A set of rules to optimise heating and cooling plant, boilers, AHUs, pumps, chillers, FCUs, VRF systems
caOptiHeatCoolRuleMasterExtAxon funcs

Registered StackHub users may elect to receive email notifications whenever a new package version is released or a comment is posted on the forum.

There are 0 watchers.

v1.0.8

caKpiRuleBoilerEff
caKpiRuleBoilerEff(cells)

Boiler efficiency calculation below:

Efficiency = (Energy Out kWh) / ((Energy In m³ * calorific value * correction factor) / conversion factor)

caRuleOptiHeatCoolStartEnd
caRuleOptiHeatCoolStartEnd(cells)

Overview

This rule runs on a equip and needs 3 points to run successfully

  1. Point with temproom tag (unit: °C)
  2. Schedule point with occupied tag
  3. weather station configured on site

Parameters

  1. target - gets from ruleOn property
  2. date - gets from spark app

Tuning Parameters

  1. leadIn - defVal:0
  2. fadeOut - defVal:0
  3. tempSeason - defVal: 15°C (<15°C = winter)
  4. tempMin - defVal: 20°C
caRuleOptiHeatCoolStartEnd
caRuleOptiHeatCoolStartEnd(cells)

Overview

This rule runs on a equip and needs 3 points to run successfully

  1. Point with temproom tag (unit: °C)
  2. Schedule point with occupied tag
  3. weather station configured on site

Parameters

  1. target - gets from ruleOn property
  2. date - gets from spark app

Tuning Parameters

  1. leadIn - defVal:0
  2. fadeOut - defVal:0
  3. tempSeason - defVal: 15°C (<15°C = winter)
  4. tempMin - defVal: 20°C
caRuleOptiRunOATControl
caRuleOptiRunOATControl(cells)
caRuleOptiRunOATControl
caRuleOptiRunOATControl(cells)
caRuleOptiRunningOutOfHours
caRuleOptiRunningOutOfHours(cells)
caRuleOptiRunningOutOfHours
caRuleOptiRunningOutOfHours(cells)
caRuleOptiSetPointOATControl
caRuleOptiSetPointOATControl(cells)
caRuleOptiSetPointOATControl
caRuleOptiSetPointOATControl(cells)